Number of inputs |
4 |
Power supply |
via the E-bus |
Technology |
U differential, I single-ended |
Signal type |
differential |
Oversampling factor |
– |
Distributed clocks |
yes |
Distributed clock precision |
<< 1 µs |
Internal resistance |
> 200 kΩ | typ. 85 Ω |
Input filter limit frequency |
5 kHz |
Common-mode voltage UCM |
max. 35 V (voltage measurement) |
Dielectric strength |
max. 30 V (current measurement) |
Conversion time |
minimum 150 µs |
Measuring range, nominal |
-10/0…+10 V | -20/0/+4…+20 mA |
Measuring range, technical |
-10.73…+10.73 V | -21.47…+21.47 mA |
Resolution |
16 bit (incl. sign) |
Measurement error/ uncertainty |
< ±0.3 % (relative to full scale value) |
Electrical isolation |
500 V (E-bus/signal voltage) |
Current consumption power contacts |
load-dependent |
Current consumption E-bus |
typ. 180 mA |
Bit width in the process image |
inputs: 16 byte |
Configuration |
no address or configuration setting |
Special features |
U/I parameterizable, ExtendedRange, standard and compact process image, activatable FIR/IIR filters |
Weight |
approx. 65 g |
Operating/storage temperature |
-25…+60 °C/-40…+85 °C |
Relative humidity |
95 %, no condensation |
Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. |
IP20/variable |
Approvals/markings |
CE, UL, ATEX, IECEx, cFMus |
Ex marking |
ATEX:
II 3G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
cFMus:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx ec IIC T4 Gc |